7/94
Horizontal bar support up to 3200 A
● Support prepared for fixing bars in horizontal position.
● Direct mounting to the structure of the enclosure, on the vertical uprights, at any
height, adjustable with a pitch of 25 mm.
● Maximum nominal rating:
– 1600 A for 5-mm bars.
– 3200 A for 10-mm bars.
● The number and the distance between supports, according to the nominal and
short-circuit current, are stated in the enclosed table.
Supply: two insulating bar supports, one metal horizontal support and fixing
elements.
Nominal
dimensions (mm)
Reference
Width/Depth (B)
500
NSYBHS500
600
NSYBHS600
800
NSYBHS800
Sets of vertical bars
Maximum distance between bar supports (mm) according to the short-circuit current Icc (kA)
Nominal
rating
In (A)
Cross-
section
(mm)
No. of
bars
per phase
15
25
30
40
50
60
65
75
85
750
60 5
1
650
325
325
217
-
-
-
-
-
900
80 5
1
650
325
325
217
-
-
-
-
-
1250
60 5
2
650
325
325
217
163
163
130
108
81
1600
80 5
2
650
325
325
217
217
163
130
108
81
1080
50 10
1
650
650
650
325
217
217
163
-
-
1250
60 10
1
650
650
650
325
325
217
163
130
108
1600
80 10
1
650
650
650
325
325
217
163
130
108
1850
50 10
2
650
650
325
325
325
217
217
217
163
2000
60 10
2
650
650
650
325
325
325
217
217
163
2500
80 10
2
650
650
650
325
325
325
325
217
163
2800
100 10
2
650
650
650
650
325
325
325
217
163
Note:
The current-carrying capacity values in the set of bars are given for an ambient temperature of 35 °C around the busbar.
The nominal rating values are indicated for IP55. The maximum values (3200 A) are achieved with ambient temperatures of less than 35 °C, varying according to
the configuration and position of the busbar.
See enclosed table of current-carrying capacities according to temperature, page
7/95
.
Busbar support accessories
For ranges
SF,
SFX
B-90
75
75
75
6,5
21
16
29
29
N
39
59,25
07_091_095_SFM054.indd 94
28/1