MT32 Underfloor pre–wired power distribution
| 39
Underfloor to desk solutions
(FBDU)
(SU)
Incoming SWA
Up to 5 protected
outgoing circuits
(SU)
Adaptors
•
Male and female can adapt existing or new boxes to MT32
Terminal or through floor box
Powertrack tap off
•
32Amp tap-off pre-wired to MT32 male connector
•
3.0m and 5.0m leads, Standard or CE
•
Also 13Amp fused tap-offs
32Amp distribution supplied by Series 507 powertrack
Product information
•
Should Series 507 powertrack be the preferred method of underfloor
power supply, then combining powertrack with MT32’s interlinked through
floor boxes and/or slave units will provide a far greater reach of floor area than
can be achieved using powertrack alone
32Amp power distribution with RCD, RCBO, MCB
protection up to 100Amp incoming supply
Product information
•
Up to 100Amps input and total FBDU load possible
•
Up to 5 independent RCBO protected zones each of which
can be isolated for maintenance or reconfiguration
•
No more need to have fused tap-offs inaccessible
below finished floor
•
More floor boxes can be supplied by one SWA cable
compared with standard powertrack
•
Floor boxes can be fitted with 2 x 2 gang 13Amp sockets for circuit
supplies above 13Amps without the need to fuse tap-offs
Floor box distribution unit (FBDU)
•
FBDU is installed flush in raised floor
to provide convenient access
•
25mm SWA gland entry
•
Up to 100Amp incoming capacity
•
Complete with main switch and RCD
•
Other MCB, RCD and RCBO types and ratings on request
•
5 x outgoing 32Amp protected circuits
•
Lockable lid on request
•
Same dimensions and trims as floor outlet boxes
A typical single 32Amp powertrack run supplies 12 to 16 floor
boxes. A single MT32 floor mounted FBDU is able to supply
up to 4 times as many floor boxes i.e. up to 50, spread
between 5 separate MCB protected circuits.
(Calculations based on a load of 2Amps per box).
Slave unit
•
Permits more floor boxes to
be fed from 1 powertrack
tap off