Marshall-Tufflex Cable Management Catalogue 2011 - page 265

Email
sales@marshall-tufflex.com
www.marshall-tufflex.com
Aluminium perimeter trunking systems
| 265
Technical information
Cable capacity chart
Compartment 1 Compartment 2 Compartment 3
No box With box No box With box No box With box
PVC power cable 1.5mm² stranded copper
Sterling Profile 1
62
186
66
62
Sterling Profile 2
62
186
66
75
Sterling Profile 3
75
186
66
75
PVC power cable 2.5mm² stranded copper
Sterling Profile 1
42
126
45
42
Sterling Profile 2
42
126
45
51
Sterling Profile 3
51
126
45
51
PVC power cable 4.0mm² stranded copper
Sterling Profile 1
32
96
34
32
Sterling Profile 2
32
96
34
39
Sterling Profile 3
39
96
34
39
Data cable: Ø5.5mm
Sterling Profile 1
17
52
19
17
Sterling Profile 2
17
52
19
21
Sterling Profile 3
21
52
19
21
Data cable: Ø6.0mm
Sterling Profile 1
14
44
15
14
Sterling Profile 2
14
44
15
18
Sterling Profile 3
18
44
15
18
Data cable: Ø6.5mm
Sterling Profile 1
12
37
13
12
Sterling Profile 2
12
37
13
15
Sterling Profile 3
15
37
13
15
Data cable: Ø7.0mm
Sterling Profile 1
10
32
11
10
Sterling Profile 2
10
32
11
13
Sterling Profile 3
13
32
11
13
Offset dimensions
The minimum set that can be
accommodated in the same plane
(from internal to external bend), is
shown below.
Dimensions
Sterling Profile 3002 - no box
Compartment 1 (total area) = 1197mm²
Compartment 2 (total area) = 3556mm² (with box)
Compartment 3 (total area) = 1451mm²
Cable capacities
• All calculations allow for a 45% space
factor.
As there can be differences between
data cable sizes, Marshall-Tufflex
recommend that cable dimensions are
confirmedwith themanufacturing
company.
MIN
90mm
G
ACT
A
C
B
28
34
50
45
14
34
81
167
1
3
2
Sterling Profile aluminium
– continued
1...,255,256,257,258,259,260,261,262,263,264 266,267,268,269,270,271,272,273,274,275,...308