PVC-U Perimeter trunking systems
Technical information
Method of continuation through a
partitionwall
Continue the main lateral run of base
through the partition wall.Fit short
lengths of cover where the trunking
passes through the partition. The
partition wall trunking is then butted
up to the main run and the joint
covered by an internal bend fitting.
Offset dimensions
The minimum set that can be
accommodated in the same plane
(from internal to external bend), is
shown below.
Cable capacities
• All calculations allow for a 45% space factor.
As there can be differences between cable sizes,
Marshall-Tufflex recommend that cable dimensions are
confirmedwith themanufacturing company.
B
36
28
50
45
87
130
fig 1
A
36
45
50
87
130
fig 2
A
B
87
50
45
87
181
Compact 3 trunking – no box
Compartment 1 total area = 3763mm²
Compartment 2 total area = 3700mm ²
Compact 2 trunking – no box
Compartment 1 total area = 1534mm²
Compartment 2 total area = 3763mm²
Compact 1 trunking – with box
Compartment 1 total area = 1280mm²
Compartment 2 total area = 1497mm²
Cable capacity chart
Compartment 1
Compartment 2
No box
With box
No box
With box
PVC power cable 1.5mm² stranded copper
Compact 1
66
–
196
78
Compact 2
80
–
196
78
Compact 3
196
78
193
76
PVC power cable 2.5mm² stranded copper
Compact 1
45
134
53
Compact 2
54
134
58
Compact 3
134
59
132
58
PVC power cable 4.0mm² stranded copper
Compact 1
34
–
101
40
Compact 2
44
–
101
40
Compact 3
101
40
100
38
Data cable: Ø5.5mm
Compact 1
19
–
56
22
Compact 2
22
–
56
22
Compact 3
56
22
55
21
Data cable: Ø6.0mm
Compact 1
16
–
47
18
Compact 2
19
–
47
18
Compact 3
47
18
46
17
Data cable: Ø6.5mm
Compact 1
13
–
40
15
Compact 2
16
–
40
15
Compact 3
40
15
39
14
Data cable: Ø7.0mm
Compact 1
11
–
34
13
Compact 2
14
–
34
13
Compact 3
34
13
34
12
Data cable: Ø8.4mm
Compact 1
9
–
29
11
Compact 2
11
–
29
11
Compact 3
29
11
28
10
Compact trunking – continued
1
2
1
2
1
2
Dimensions
90min